Product Video
Advantage
Warranty: 2 years
Manual Operation: Full range of products are equipped with hand wheel opearting mechanism to facilitate the commissioning and emergency manual opeartion, manual/ electric automatic switching, safe and reliable.
Infrared remote control: The intelligent type actuator is able to provide different remote conrol based on different application requirements. Such as portable infrated remote control in ordinary locations and explosion-proof remote control for hazardous locations.
Operational Safety: F grade (H grade is optional) insulation motor. The motor windings are equipped with temperature control switches to sense the temperature of the motor and provide over temperature protection, which ensures the operational safety of the motor.
Anti-humidity Resistance: Installed with heater inside the actuator used to remove the internal condensation which cause damages to electrical parts.
Phase Protection: Phase detection and correction functions avoid the actuator being damaged by connecting to the wrong power phase.
Standard Specification
Force range |
1000-25000N |
Max stroke |
100mm |
Running time |
55-179S |
Ambient temperature |
-25°C---+70°C |
Anti-vibration level |
JB/T 8219 |
Noise level |
Less than 75dB within 1m |
Electrical interface |
Two PG16 |
Ingress Protection |
IP67 |
Optional |
IP68 |
Motor Specifications |
Class F.with thermal protector up to +135°C optional:Class H |
Working System |
On/off type, S2-15min, no more than 600 times per hour start; |
Modulating type |
S4-50%, up to 600 triggers per hour; |
Optional |
1200 and 1800 times per hour. |
Applicable Voltage |
4V-240V; |
Single phase |
DC24V2 |
Bus |
Modbus |
Input signal |
On/off type,20-60VAC/DC or 60-120VAC; Optoelectronic isolation; Modulating type. |
Input signal |
4-20mA; 0-10V; 2-10V;Accuracy 1%; |
Dead zone |
0-25.5% adjustable rate in full stroke. |
Input impedance |
75Ω(4-20mA) |
Signal Feedback |
On/off |
Type RexayX5 |
1.on/off in place;2.on/off over torque; 3.Local/remote;4.Center position;5.Multiple malfuntions to choose from;Optional:4-20mA transmit. |
Malfunction Feedback |
On/off,typeTorqueprotection;Motor,overheat protection;Jammed,valve,protection; Instantaneous,reverse,protection;Broken,signal protection; Other alarms |
Output Signal |
4-20mA; |
Modulating type |
0-10V; |
Output signal |
2-10V; |
Output impedance |
≤750Ω(4-20mA) |
Indication |
Stroke indicator |